Automatic charging and pre-start device with a graphic ÆÊ display Vympel-55 for automotive lead-acid batteries and general-purpose alkaline batteries. Manual
Profile selection and configuration
(The C.D. must be disconnected from the battery)
1. Insert the plug into a mains socket. Switch on the POWER switch.
2. Select the charging algorithm and set the current and voltage values.
3. Disconnect the device from the mains.
Connection to the battery
ATTENTION! Observe the order of connecting the charger (C.D.) to the battery. GOST IEC 60335-2-29-2012 §7.12
FAILURE TO FOLLOW THE CONNECTION ORDER MAY CAUSE THE C.D. TO FAIL.
1. Connect the C.D. clamp with the red insulator to the (+) terminal of the battery.
2. Connect the C.D. clamp with the black insulator to the (-) terminal of the battery.
3. Insert the plug into the mains socket. Switch on the POWER switch.
ATTENTION!
The device is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities or lacking experience and knowledge unless they are supervised or instructed regarding the use of the device by a person responsible for their safety. Children must be supervised to prevent playing with the device.
PURPOSE
The primary purpose of the charger (C.D.) is automatic charging of storage batteries (S.B.) of the following types:
6-volt lead-acid S.B.
12-volt lead-acid S.B. in buffer mode
12-volt lead-acid marine and traction S.B.
12-volt lead-acid automotive S.B.
12-volt alkaline S.B.
Sealed lead-acid S.B.
Of any capacity, including fully discharged (down to zero).
In automatic mode, the device monitors and limits the voltage on the S.B. being charged, preventing intensive gas generation (boiling) and overcharging of the S.B. Therefore, the device can be used to charge modern maintenance-free batteries and does not require disconnecting the S.B. being charged from the vehicle’s on-board network.
It is also possible to use the charger in non-automatic mode for charging storage batteries of any electrochemical system with a maximum end-of-charge voltage below 18 V.
The C.D. Vympel-55 allows you to adjust the charging current, adjust the voltage and select the charging algorithm, and to save the set parameters in profiles for convenient quick switching when charging different types of batteries.
Additionally, the charger can be used as a multi-purpose DC power source for powering automotive equipment, power tools, halogen lamps, and other devices and instruments.
The automatic charger is designed for indoor use only, degree of water protection IP standard (Ingress Protection rating) IP20.
.TECHNICAL SPECIFICATIONS
| Mains supply voltage, frequency 50–60 Hz | 180 V – 240 V |
| Output current adjustment ranges | at least 0.5–15 A |
| Output voltage in current stabilization mode (equal to the voltage at the accumulator terminals) | 0 – 18 V |
| Output voltage adjustment range in voltage stabilization mode (when the load current is less than the value set in settings) | 5.5 – 18 V |
| Voltage setting tolerance | 1% |
| Current setting tolerance | 2.5% |
| Operating temperature range | from -10 °C to +40 °C |
| Overall dimensions | 155x85x200 mm |
| Mass | 0.83 kg |
| Built-in micro-fan | + |
| Indicator type | graphic liquid-crystal indicator with backlight |
DEVICE DESIGN
Structurally, the charger is made in a plastic housing with ventilation louvers.
The mains cord and output leads with clamps are placed in the rear compartment of the housing.
The front panel includes:
1 – liquid-crystal indicator with backlight
2 – control buttons ˂ / ˃
3 – navigation and settings buttons ˄ / ˅
4 – mains switch
The electronic circuit of the charger is a push-pull high-voltage high-frequency converter with pulse-width modulation, featuring a control circuit with two feedback loops for output current and voltage. This power section design ensures high efficiency over a wide input voltage range, nearly ideal output characteristics of a current generator and a voltage generator, reliable galvanic isolation, as well as high specific mass-dimensional and power characteristics.
A graphic liquid-crystal indicator with backlight is used to display the charging current and voltage. To protect the power section from overheating, a micro-fan and an output current limiting circuit are employed. This circuit automatically reduces the output current when the internal temperature rises above normal. When the normal temperature is restored, the current adjustment range is restored.
SAFETY REQUIREMENTS
Before starting operation of the C.D., read this manual as well as the rules for care and operation of S.B. Before connecting the device to the mains, make sure that the insulation of the mains cord is intact (no damage). Do not allow chemically active liquids (gasoline, acid, etc.) or water to contact the C.D. housing and mains cord or the C.D. output leads. During charging, the S.B. must be placed in a well-ventilated area. The gases and acid aerosol emitted by the S.B. must not be directed toward the C.D., its output leads, or its mains cord.
ATTENTION!!! Although the Vympel-55 charger user guide does not require your participation during charging of the accumulator, leaving the connected C.D. unattended is unacceptable, as with any complex equipment, especially when powered from a garage electrical network.
FUNCTIONAL CHECK
Remove the leads. Make sure the housing is free of mechanical damage and the insulation of the wires is intact.
To check C.D. operability without a storage battery, connect it to the AC mains. The output terminals must be open.
Switch on the “Power” switch. Make sure the “Power” switch LED indicator is lit.
Verify that a profile with algorithm 1 is selected, the voltage is within 12–16 V, and the current within 8–15 A.
Short the output clamps or, for clarity, connect a 55–110 W automotive incandescent lamp to them; make sure the current and voltage readings change and the lamp lights.
To check fan operation, set the current to at least 11.5 A, short the terminals and make sure the fan operates.
Attention! The micro-fan turns on automatically when the internal temperature rises or the current exceeds 11 A. In short-circuit mode (output terminals shorted together) slight humming or noise is possible.
.OPERATING PROCEDURE
CHARGING A STORAGE BATTERY IN AUTOMATIC MODE
If the ORION Vympel-55 charger has a profile selected with charging parameters corresponding to the battery type being charged, proceed to connection and charging of the S.B.
Profile selection and configuration
(The C.D. must be disconnected from the battery)
1. Connect the Vympel-55 charger user guide device to the AC mains. Switch on the POWER switch.
2. Select a properly configured profile (go to item 7) or modify a profile.
3. Select the charging algorithm (see Fig. 2. Operating graphs of the C.D. when charging lead-acid S.B. in automatic mode).
4. Set the voltage according to the table or the S.B. datasheet.
CHECK THE MAXIMUM PERMISSIBLE END-OF-CHARGE VOLTAGE IN THE STORAGE BATTERY PASSPORT/DATASHEET.
| Battery type | WET batteries | EFB batteries | ||
| antimony | silver | some types | ||
| End-of-charge voltage | 14.4–14.6 | 14.7–15.5 | 15.6–16.2 | 14.5–15.0 |
| Battery type | VRLA | Alkaline S.B. | ||
| AGM | GEL batteries | |||
| Long Life | Deep Cycle | |||
| End-of-charge voltage | 14.2–14.8 | 13.8–14.1 | 14.1–14.4 | 17.5–18.0 |
Recommended voltages for automatic charging of various S.B. types:
for 6-volt lead-acid S.B. ............................... 7.5 V
for 12-volt lead-acid S.B. in buffer mode ... 13.8 V
for 12-volt lead-acid marine and traction S.B. ... 14.4 V
for 12-volt lead-acid automotive S.B. .... 14.8–15 V
for 12-volt calcium S.B., e.g., VARTA ............ 16 V
for 12-volt alkaline S.B. ............................. 18 V
for sealed lead-acid S.B. ............. see S.B. passport/datasheet
5. Set the current corresponding to the type and capacity of the battery being charged (common recommendation: 0.1 of the battery capacity).
6. If necessary, set the timer.
7. Disconnect the device from the mains.
Connecting to the battery and charging in automatic mode
Failure to follow the connection order may cause the charging device to fail or an explosion of gases released by the battery. Connect and disconnect the C.D. in accordance with GOST requirement §7.12 — “The battery terminal, IEC 60335-2-29-2012 not connected to the chassis, shall be connected to the charger first; the other connection shall be made to the chassis away from the battery and fuel line; then the battery charger shall be connected to the supply mains. After charging, the battery charger shall be disconnected from the supply mains; then the charger shall be disconnected from the chassis; then — from the battery”.
1. Connect the C.D. clamp with the red insulator to the (+) terminal of the battery.
2. Connect the C.D. clamp with the black insulator to the (-) terminal of the battery.
3. Connect the C.D. to the AC mains. Switch on the POWER switch.
The algorithm starts operating 50 seconds after the indicator is turned on. If necessary, you can restart the charging algorithm; the procedure is described in the section Charger control.
4. Charging the storage battery will proceed in automatic mode with the current set in the profile (Fig. 2, interval II on the graph).
Current change for algorithms 4 and 5 (only for algorithms 4 and 5, Fig. 2, interval III on the graph). When the battery voltage reaches Volt 2, the current changes to Current 2.
Current reduction (Fig. 2, interval IV on the graph). When the S.B. reaches voltage = Volt 1, the current automatically changes according to the selected charging algorithm. The beginning of the reduction of the set current indicates that the battery has reached 75–95% charge. For full topping charge, an additional half-hour to several hours may be required (depending on the type, capacity, and technical condition of the S.B.).
Buffer mode (Fig. 2, interval V on the graph). During the topping charge, the C.D. switches to buffer mode, in which the S.B. self-discharge is compensated by the required charging current.
Spontaneous current decrease at the beginning of charging may indicate sulphation of the S.B. plates. By reducing the current, the C.D. automatically switches to S.B. desulfation mode. Depending on the degree of plate impairment, desulfation may take from several minutes to several hours. During desulfation, the current will gradually and automatically increase to the set value.
The duration of operation in buffer mode is unlimited and even beneficial for used batteries, as after several tens of hours most S.B. improve and restore their key characteristics — Battery internal resistance and Battery capacity.
5. Upon completion of charging, disconnect the C.D. from the mains and remove the clamps. It is recommended to wipe the clamps and leads with a damp, then dry cloth to remove any electrolyte. It is advisable to lubricate the clamps afterwards with any automotive grease to protect against corrosion.
.Operating graphs of the C.D. when charging lead-acid S.B. in automatic mode
Legend
Volt1 — Upper voltage threshold (voltage stabilization or current shutdown).
Volt2 — Voltage at which the value of Current changes to Current 2 (only algorithms 4 and 5)
Volt3 — Lower voltage threshold (buffer mode stabilization or current turn-on)
Current — Current value set at the beginning of charging
Current 2 — Current value set when Volt2 is reached.
Algorithm 1
I — connection, restart of charging algorithm
II — charging with the set current
IV — upon reaching Volt, the C.D. stabilizes the set voltage (current decreases automatically)
V — charging is complete when the current decreases to 0.5–1 A.
Algorithm 2
I — connection, restart of charging algorithm
II — charging with the set current
IV — upon reaching Volt1, the C.D. automatically reduces the stabilization voltage to Volt3; thereafter the set voltage is stabilized (current decreases automatically)
V — charging is complete when the current decreases to 0.5–1 A
Algorithm 3
I — connection, restart of charging algorithm
II — charging with the set current
III — upon reaching Volt1, the current switches off; when the S.B. voltage drops to Volt3 the current switches on; the process then repeats
IV — charging is complete; pauses between current pulses are much longer than current flow time.
Algorithm 4
I — connection, restart of charging algorithm
II — charging with the set current (Current 1)
III — when voltage = Volt2 is reached, the current changes to Current 2
IV — upon reaching Volt1, the C.D. automatically reduces the stabilization voltage to Volt3; thereafter the set voltage is stabilized (current decreases automatically)
V — charging is complete when the current decreases to 0.5–1 A
Algorithm 5
I — connection, restart of charging algorithm
II — charging with the set current (Current 1)
III — when voltage = Volt2 is reached, the current changes to Current 2
IV — upon reaching Volt1, the current switches off; when the S.B. voltage drops to Volt3, the current switches on; the process then repeats
V — charging is complete; pauses between current pulses are much longer than current flow time.
5. Upon completion of charging, disconnect the C.D. from the mains and remove the clamps. It is recommended to wipe the clamps and leads with a damp, then dry cloth to remove any electrolyte. It is advisable to lubricate the clamps afterwards with any automotive grease to protect against corrosion.
Attention! Upon connection or restart of the charging algorithm (interval I on the graph), the C.D. records the voltage and holds the minimum current for 30–60 seconds. All connections must be made during this period. Thereafter, the C.D. operates according to the selected algorithm.
USING THE AUTOMOTIVE CHARGER ORION Vympel-55 AS A MULTI-PURPOSE POWER SUPPLY
The C.D. is a stabilized DC voltage source with limiting (stabilization) of the load current. Therefore, it can be used to power any loads requiring 5.5–18 V with a total current consumption less than the value set on the charger. In case of overload or short circuit of the C.D. output leads, the device will switch to current stabilization mode. To operate as a multi-purpose power supply, select algorithm 1 in the profile settings.
USING THE C.D. AS A PRE-START DEVICE
To facilitate engine start, connect the charger Vympel-55 to the S.B. (see section Charging the S.B. in automatic mode), set the maximum current. In this way, revive the battery for 5–30 minutes, and then, without disconnecting the C.D., start the engine. A battery revived by pre-start charging is capable of delivering a significantly higher current in the first seconds of starter operation. This allows easy overcoming of viscous oil, creating good mixture formation and spark by fast cranking (combustion in a diesel), and in most cases eliminates the need for an expensive starting device; reduced cranking time reduces the load on the S.B., extending its service life. If unsuccessful, repeat the procedure. The manufacturer recommends more powerful models for this purpose (Vympel-30, Vympel-40, Vympel-50, Vympel-55 or several C.D. units connected in parallel).
.NON-AUTOMATIC CHARGING MODE
Non-automatic mode is a charging mode in which the S.B. end-of-charge voltage is lower than the voltage the C.D. can produce.
If a profile with charging parameters corresponding to the battery type is selected in the C.D., proceed to connection and charging of the S.B.
Profile selection and configuration
(The C.D. must be disconnected from the battery)
1. Connect the C.D. to the AC mains. Switch on the POWER switch.
2. Select a properly configured profile (go to item 7) or modify a profile.
3. Select the charging algorithm (see Fig. 2. Operating graphs of the C.D. when charging lead-acid S.B. in automatic mode).
4. Set the voltage higher than the maximum permissible for the given battery.
5. Set the current corresponding to the type and capacity of the battery being charged (common recommendation: 0.1 of the battery capacity).
6. If necessary, set the timer.
7. Disconnect the device from the mains.
Connection to the battery and charging in non-automatic mode
Failure to follow the connection order may cause the C.D. to fail or an explosion of gases released by the battery. Connect and disconnect the C.D. in accordance with GOST IEC 60335-2-29-2012 §7.12 (see section Charging the S.B. in automatic mode).
1. Connect the C.D. clamp with the red insulator to the (+) terminal of the battery.
2. Connect the C.D. clamp with the black insulator to the (-) terminal of the battery.
3. Connect the automotive charger to the AC mains. Switch on the POWER switch. The algorithm starts 50 seconds after the indicator is turned on. If necessary, you can restart the charging algorithm; the procedure is described in the section Charger control.
4. Charging of the S.B. will occur in non-automatic mode. In this mode, it is necessary to monitor the state of charge by commonly accepted methods (by voltage, by time and current, by electrolyte density, etc.).
5. Upon completion of charging, disconnect the C.D. from the mains and remove the clamps. It is recommended to wipe the clamps and leads with a damp, then dry cloth to remove any electrolyte. It is advisable to lubricate the clamps afterwards with any automotive grease to protect against corrosion.
The operating time of the charger ORION Vympel-55 in any of the listed modes is unlimited.
MAIN MODES — CHARGER CONTROL
Control of the charger is performed using four buttons: ˂ / ˃ and ˄ / ˅. See Fig. 1.
☞ — single short press
☛ — long press
☞ ☞ — several short presses
☛ ˃ — (right) go to settings mode
☞ ˃ — in settings mode go to parameter editing
☞ ˃ — save the value after editing
☞ ˄ / ˅ — (up or down) select a menu item
☞ ˄ / ˅ — change a number in the edit menu
☛ ˄ / ˅ — a long press automatically changes a number in the edit menu (current, voltage, etc.)
☛ ˂ — (left) return to the previous level (on exit from editing, changed values will not be saved)
☞ ☞ ˂ — return to the working display
WORKING DISPLAY
The screen shows the current and voltage. The working display is shown automatically if the C.D. buttons have not been pressed for some time. It can be called up manually by one or several presses of the ˂ button.
☞ ☞ ˂ — go to the working display.
INFORMATION STRING
On the C.D. display, additional information can be shown: current state, charging time, amount of energy delivered to the battery. The information is displayed at the bottom of the screen as a pop-up string.
Enable/Disable the information string
Go to the working display
☞ ˄ — enable display of the string
☞ ˄ — press again to remove the string from the working display
The information string can also be enabled/disabled via the settings menu.
PROFILE SELECTION
The charger contains several sets of parameters, each set is called a “profile”. A profile allows saving the current, upper voltage threshold, lower voltage threshold, and charging algorithm values. Each profile can be configured individually for various battery types.
PROFILE SELECTION AND ACTIVATION
Activating a profile will change the charging parameters. The active profile is marked with a dot. For example, we need profile No. 2.
Go to the working display
☞ ˃ — enter PROFILE selection
☞ ˄ / ˅ — select the required PROFILE
☞ ˃ — enter profile editing
☞ ˄ / ˅ — select activation
☞ ˃ — activate the profile
The C.D. will now change current and voltage settings according to the selected profile.
.PROFILE CONFIGURATION
Go to the working display
☞ ˃ — enter PROFILE selection
☞ ˄ / ˅ — select the required PROFILE
☞ ˃ — enter profile editing; the first parameter is CURRENT
Selecting a charging algorithm
☞ ˄ / ˅ — select CHARGING ALGORITHM
☞ ˃ — enter algorithm selection
☞ ˄ / ˅ — select the required algorithm (1–5) (see Fig. 2. Operating graphs of the C.D. when charging lead-acid S.B. in automatic mode)
☞ ˃ — confirm
☛ ˂ — exit the algorithm selection mode
Editing the current
☞ ˄ / ˅ — select CURRENT
☞ ˃ — enter editing
☛ ˄ / ˅ — set the desired value
☞ ˃ — save the value
Editing Current 2
(Only for algorithms 4 and 5)
☞ ˄ / ˅ — select CURRENT 2
☞ ˃ — enter editing
☛ ˄ / ˅ — set the desired value
☞ ˃ — save the value
Upper voltage threshold
(Voltage stabilization or current shutdown)
☞ ˅ — select VOLT 1 — setting the upper voltage threshold
☞ ˃ — enter threshold editing
☛ ˄ / ˅ — set the desired upper threshold value*
☞ ˃ — save the value
The upper and lower voltage thresholds must differ by at least 0.5 V. If it is impossible to set the desired value for one threshold, check the value of the other threshold and adjust so that the difference between the thresholds is more than 0.5 V.
Lower voltage threshold
(Buffer mode stabilization or current switch-on. When algorithm 1 is selected, this menu item is absent)
☞ ˅ — select VOLT 3 — setting the lower voltage threshold
☞ ˃ — enter threshold editing
☛ ˄ / ˅ — set the desired lower threshold value*
☞ ˃ — save the value
Voltage for current change
(Voltage at which the current value CURRENT changes to CURRENT 2. Only for algorithms 4 and 5)
☞ ˅ — select VOLT 2 — setting the threshold for current change
☞ ˃ — enter threshold editing
☛ ˄ / ˅ — set the desired value
☞ ˃ — save the value
Profile activation
☞ ˄ / ˅ — select ACTIVATE
☞ ˃ — activate the profile
☛ ˂ — exit settings mode
The C.D. will now change current and voltage settings in accordance with the values that have been set.
RESTARTING THE CHARGING ALGORITHM
If it is necessary for the C.D. to start operation from the very beginning according to the charging graph, the charging algorithm must be restarted. See charging graphs in Fig. 2.
Go to the working display
☞ ˃ — enter PROFILE selection ☞ ˄ / ˅ — select RESTART ☞ ˃ — restart the charging algorithm
Attention! Upon connection or restart of the charging algorithm (interval I on the graph), the C.D. records the voltage and holds the minimum current for 30–60 seconds. All connections must be made during this period. Thereafter, the automatic charger operates according to the selected algorithm.
SETTINGS
BACKLIGHT BRIGHTNESS
Allows changing the display backlight brightness.
Go to the working display
☞ ˄ / ˅ — select SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — select BRIGHTNESS
☞ ˃ — enter editing
☞ ˄ / ˅ — set the brightness level ☞ ˃ — save the value
SOUND SETTINGS
Allow disabling button press sounds.
Go to the working display
☞ ˄ / ˅ — select SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — select BUTTON SOUND
☞ ˃ — enable button sound — CHECK MARK shown, or disable sound — NO CHECK MARK
MINIMUM INDICATED CURRENT
Set current values from 0 to 0.5.
Go to the working display
☞ ˄ / ˅ — select SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — select ADVANCED
☞ ˃ — enter settings☞
˄ / ˅ — select MINIMUM CURRENT
☞ ˃ — proceed to setting
☞ ˄ / ˅ — set the minimum indicated current value
☞ ˃ — confirm
FAN OPERATING MODE
The fan can run continuously or switch on periodically when the internal temperature reaches the set threshold.
Go to the working display
☞ ˄ / ˅ — select SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — select ADVANCED SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — select FAN
☞ ˃ — select MODE (the active mode is shown in the lower line; by default AUTO with a 70 °C threshold is set)☞ ˃ — press again to configure or change
Then select the fan operating mode:
The fan turns on automatically when the internal temperature reaches the set value.
☞ ˄ / ˅ — select AUTO
☞ ˃ — activate the mode
☞ ˄ / ˅ — select THRESHOLD
☞ ˃ — proceed to setting
☞ ˄ / ˅ — set the temperature threshold value
☞ ˃ — confirm
The fan runs continuously.
☞ ˄ / ˅ — select CONTINUOUS
☞ ˃ — activate the mode
INFORMATION STRING
See the section: Information string, p. 15.
SOFTWARE VERSION
Go to the working display
☞ ˃ — enter PROFILE selection
☞ ˄ / ˅ — select SETTINGS
☞ ˃ — enter settings
☞ ˄ / ˅ — INFORMATION
☞ ˃ — view the SOFTWARE VERSION
The manufacturer reserves the right to change the software without notifying the end user.
TIMER
The timer allows turning the source on with a programmable delay and/or turning the charging off after a specified time, as well as starting another profile. Settings are saved in memory and will not need to be re-entered on restart. Possible combinations are shown in the graph. If the timer is enabled, the C.D. will switch on/off according to the programmed values. If the timer is disabled, the charger will operate continuously. During delay and off states, the charger sets current to 0.5 A and voltage to 5.0 V.
Operating graphs of the C.D. depending on timer settings
Fig. 3
Continuous charging
![]() |
|
| timer operation — no (off) delay — any |
charging time — any action — any |
Fixed charging time
![]() |
|
| timer operation — yes (on) delay — 0 h : 0 m : 0 s |
charging time — any action — off |
Charging and switching to another profile
![]() |
|
| timer operation — yes (on) delay — 0 h : 0 m : 0 s |
charging time — any action — profile (1,2,3) |
Continuous charging with delayed start
![]() |
|
| timer operation — yes (on) delay — any |
charging time — 0 h : 0 m : 0 action — off |
Fixed charging time with delayed start
![]() |
|
| timer operation — yes (on) delay — any |
charging time — any action — off |
Fixed charging time with delayed start and switch to another profile
![]() |
|
| timer operation — yes (on) delay — any |
charging time — any action — profile (1,2,3) |
Periodic recharge
![]() |
|
| timer operation — yes (on) delay — any |
charging time — any action — periodic start |
VIEWING TIMER STATUS AND OPERATING TIME
Go to the working display
The screen will display the time remaining until the state change (switching the source on or off).
TIMER CONFIGURATION
Go to the working display
☞ ˃ — enter PROFILE selection
☞ ˄ / ˅ — select TIMERS
☞ ˃ — enter timer setup
Setting the delay
☞ ˄ / ˅ — select DELAY — (time after which S.B. charging will start)
☞ ˃ — enter delay setting
☞ ˄ / ˅ — select HOUR — enter hour setting
☛ ˄ / ˅ — set hours
☞ ˃ — save the hour setting
☞ ˄ / ˅ — select MIN
☞ ˃ — enter minute setting
☛ ˄ / ˅ — set minutes
☞ ˃ — save the minute setting
☞ ˄ / ˅ — select SEC
☞ ˃ — enter second setting
☛ ˄ / ˅ — set seconds
☞ ˃ — save the second setting
☞ ˂ — exit the delay setting
Setting the charging time
☞ ˄ / ˅ — select CHARGE
☞ ˃ — enter charging time setting (Configure similarly to delay)
Selecting the action after the timer finishes
1. OFF — turn the C.D. off (the charger sets current to 0.5 A and voltage to 5.0 V)
2. RESTART — periodic recharge (cyclic on/off of the source)
3. PROFILE 1,2,3 — start the selected profile
☞ ˄ / ˅ — select ACTION
☞ ˃ — proceed to action selection
☞ ˄ / ˅ — select the required action
☞ ˃ — confirm selection
Starting the timers
☞ ˄ / ˅ — select ACTIVATE
☞ ˃ — switch the timer on — CHECK MARK shown, or switch off — NO CHECK MARK
ENABLING THE TIMER WITH SAVED SETTINGS
Go to the working display
☞ ˃ — enter PROFILE selection
☞ ˄ / ˅ — select timer
☞ ˃ — enter timer setup
☞ ˄ / ˅ — select ACTIVATE
☞ ˃ — CHECK MARK SET
LEAD RESISTANCE CALIBRATION
For correct voltmeter operation when installing output leads of a different length, it is necessary to calculate and compensate their resistance.
A procedure for more accurate calibration of lead resistance has been added to the charger, along with the option of manual setting.
To enter the lead resistance setting menu from the main screen, perform the following:
☞ ˃ — enter profile selection
☞ ˄ / ˅ — select settings
☞ ˃ — enter settings
☞ ˄ / ˅ — select Advanced
☞ ˃ — enter Advanced
☞ ˄ / ˅ — select Lead resistance
☞ ˃ — enter Lead resistance
The lead resistance settings menu looks as follows (actual values may differ from those shown):
Automatic calculation
The device allows calculating the voltage automatically based on the entered voltage and the current value.
Attention: for automatic calculation, perform the following steps beforehand:
Set charging algorithm 1 in the active profile
Set current in the active profile to at least 10 A (preferably set the maximum; the higher the current, the lower the error)
Connect a discharged battery or a load of approximately 150 W so that the actual current differs from the set current by no more than 0.3 A. For a load, you may use, for example, several headlight lamps connected in parallel.
After these conditions are met, while in the lead resistance menu perform the following:
Measure the voltage at the battery terminals with an external instrument
☞ ˄ / ˅ — select VOLT
☞ ˃ — enter voltage editing
☞ ˄ / ˅ — set the voltage corresponding to the readings of the external instrument
☞ ˃ — save the set value
After saving, if no errors occur, the RES field will contain a new calculated value of lead resistance in milliohms.
Possible errors
On saving, the device may show an error. For example:
Possible error codes and corrective actions are listed below:
Error 2: the difference between the set and actual current exceeds 0.3 A, as the device switched to voltage stabilization mode. Remedy: Increase the load.
Error 3: current less than 10 A. Remedy: Set current of 10 A or more in the active profile.
In case of an error, the lead resistance value does not change.
Manual setting
In addition to the automatic calculation of lead resistance, it is possible to set it manually. To do this:
☞ ˄ / ˅ — select RES
☞ ˃ — enter lead resistance editing
☞ ˄ / ˅ — set the required value (in milliohms)
☞ ˃ — save the set value.
REVERSE POLARITY PROTECTION
The C.D. has electronic reverse polarity protection. In case of incorrect connection, the C.D. disconnects from the battery, a message appears on the screen and a periodic signal sounds. After disconnecting the C.D. clamps from the battery, operability is restored automatically.
OVERHEAT PROTECTION
To protect the power section from overheating, a micro-fan and an output current limiting circuit are used. This circuit automatically reduces the output current when the internal temperature rises above normal. A message appears on the screen and a periodic signal sounds. After the internal temperature decreases, the source returns to normal operation.
Fan operating mode is changed according to the section (p. 20). Fan operating mode
PREVENTIVE MAINTENANCE AND REPAIR
During long-term operation of the C.D., it is recommended to periodically perform the following maintenance:
1. Remove corrosion traces and lubricate the crocodile clamps.
2. Clean the louvers of dust by blowing.
3. Check the integrity of the mains cord insulation.
More complex work involving disassembly of the C.D. housing, such as replacement of the mains cord in case of damage, must be performed by the C.D. manufacturer or its agent or a similarly qualified person.
Standard service life of the C.D. — 5 years
The manufacturer reserves the right to make changes to the device design and its characteristics.
WARRANTY OBLIGATIONS
The product complies with the requirements of normative documents: GOST 30805.14.1, IEC 60335-2-29-2012; 2013 GOST 30805.14-2013; GOST 30804.3.2-2013; GOST 30804.3.3-2013 and has a Certificate of Conformity of the Customs Union L16 09524 dated 6.2.6 RU C-RU.A.B.201. The manufacturer guarantees the operability of the device when all requirements stated in the operation manual are observed.
The warranty period of operation is 12 months from the date of sale. During the warranty period, the manufacturer repairs the device free of charge. Without a warranty card, in case of mechanical damage, and if a malfunction is caused by improper operation, claims for device performance are not accepted and warranty repair is not provided. In case of malfunction while observing all requirements, repair (exchange) of the device is performed at the place of sale.
Organization ____________________________________
Date of sale ____________________________________
ATTENTION TO COUNTERFEITS!
Please be informed that low-quality chargers have appeared on the consumer market, with packaging, graphic design solutions, and appearance extremely similar to the design and solutions of our company’s products.
When selecting products, please pay special attention not only to the appearance of the packaging but also to the name of the product manufacturer.
We inform you that we can vouch for the quality and safety only of those chargers manufactured by NPP “Orion” (Saint Petersburg).
Vympel operation manuals |
| Vympel-20 charger |
| Vympel-30 charger |
| Vympel-57 charger |
| Vympel-150 charger |






