XH-W3001 Temperature Controller User Manual in English
This operating manual describes the design, technical specifications, and operating procedures for the XH-W3001 controller (temperature regulator).
Read this manual carefully before installing the device in the system to be controlled.
The device is recommended for operation at ambient temperatures from -10 to +60°C and relative humidity of 45–85%.
Intended Use
The XH-W3001 controller (temperature regulator) is designed to monitor and maintain the temperature of industrial, technical, and household equipment. It has two relays and can control a heater and a refrigerator simultaneously.
The temperature sensor is an NTC thermistor with a 1 m connection cable. The sensor is included with the device.
Main Features
• Switches between cooling and heating modes;
• Controls temperature by setting a target value and a differential value;
• Temperature calibration;
Technical Specifications
Temperature control range: -50°C to 110°C
Temperature measurement accuracy: ± 0.2 C
Temperature control accuracy: ± 0.1 °C
Input sensor: NTC 10K L-probe, 1 m long, waterproof
Supply voltage: according to the selected version (12 V / 24 V / 220 V)
Output power: according to the selected version (120 W / 240 W / 1500 W)
Output current: up to 10 A
Dimensions: 60 x 45 x 31 mm
Safety Instructions
(!) Warning! The device uses a supply voltage that is dangerous to human life.
Disconnect the mains supply before making connections, servicing, or repairing the device.
Only qualified personnel who have read this manual may install the device or connect it to the mains and load. Insulate all connections thoroughly and cover all live parts.
Do not allow moisture to reach the terminal block contacts or enter the device.
When operating and servicing the device, follow the Rules for the Technical Operation of Consumer Electrical Installations and the Electrical Safety Rules.
When using the device with a heating element, fan heater, convector, or similar equipment, make sure that the equipment is grounded.
Clearly distinguish the sensor wire, power supply wires, and output relay interface. Do not connect them incorrectly or overload the relay.
Do not use the device in conditions of high humidity, high temperature, strong electromagnetic interference, or severe corrosion.
The power supply must match the voltage specified in the specifications.
To avoid interference, keep the sensor cables and power cable sufficiently far apart.
If the thermostat and heater are used to control the temperature in a damp room, such as a cellar, basement, or greenhouse, take additional safety precautions: use cables with reliable, double PVC insulation; secure all cables in cable ducts; and place any cable on the floor in a protective conduit.
(!) Disconnect the thermostat from the mains before entering the room.
(!) Remember that damp rooms present an increased safety hazard.
.Warning!
Before connecting the device to the mains, check its supply voltage rating: AC220V, AC110-220V, DC24V, or DC12V.
Before operation, connect the input and output wires correctly, observing polarity and the markings on the device housing.
The red input wire is positive and the black wire is negative. The yellow output wire is positive and the black wire is negative.
Use the Up and Down buttons to adjust the temperature.
Press Up to display the first temperature level. Press Down to display the second temperature level.
Control Panel and Indicators
1. Temperature value
2. Up (increase) button
3. Output indicator
4. Down (decrease) button
5. Thermostat model
Setting the Switch-On Temperature
Press the Down button ONCE to continue setting the temperature;
Press and hold the Up button for more than 3 seconds until the value appears on the display and stops flashing. Then press Up or Down to set the switch-on temperature. Wait until the value stops flashing.
Setting the Switch-Off Temperature
Press and hold the button for more than 3 seconds until the value appears on the display and stops flashing. Then press Up or Down to set the switch-off temperature. Wait until the value stops flashing.
Setting Hysteresis
The XH-W3001 thermostat lets you set hysteresis from 0 to 10. For example, if the switch-on temperature is set to 35 degrees and the switch-off temperature to 40 degrees, setting hysteresis to 5 degrees adds 5 degrees to the switch-off temperature, and the thermostat switches off at 45 degrees. We recommend a hysteresis value of 0.3.
Restoring Factory Settings
With the power on, press and hold the Up and Down buttons simultaneously. The display shows 888, and the controller then automatically switches to temperature detection.
Troubleshooting
If the display shows 3 Latin letter L characters, this indicates a problem with the thermistor sensor. Check the sensor and its wires for continuity. Replace the thermistor if necessary.
If the XH-W3001 thermostat display shows 3 Latin letter H characters, the temperature around the thermistor is outside its operating limits. Check the temperature sensing point. Move the thermistor sensor away from the hot or cold area.
Warranty
The warranty period is 12 months from the date of sale.
If the device fails during this period while the user has complied with the operating instructions, the supplier will repair or replace it free of charge. The warranty does not cover products with external damage to the device housing or sensor, or regulator components damaged by incorrect wiring of live conductors, exceeding the permitted load power, or a short circuit.